In the frequency changer must carry on the high
efficiency diode rectification, the high efficiency transistor
inverts, the result is produces the electric current higher harmonic
in the input output circuit, the disturbance power supply system, the
load and other neighbor electrical equipments. In the actual use
process, frequently meets the frequency changer harmonic interference
question, following simple introduction overtone produces mechanism,
dissemination way and effective suppression disturbance method. 1. frequency changers overtones produce the mechanism The frequency changer main circuit generally for
hands over - is straight - hands over the composition, exterior inputs
380V/50Hz the labor frequency power source to become the DC voltage
signal after the three-phase bridge connection not controllable
rectification, inverts after the filter electric capacity filter and
the high efficiency transistor on-off element for the frequency
invariable exchange signal. In the rectification return route,
the input current profile for the irregular rectangular wave, the
profile decomposes according to the Fourier progression into the
fundamental wave and each 次谐? higher harmonic will disturb the
input power supply system. In the inversion output circuit, the
output current signal is the PWM intelligence signal modulation pulse
profile, regarding the GTR high efficiency inversion part, its PWM
carrier frequency is 2 ~ 3kHz, but IGBT the high efficiency inversion
part PWM highest carrier frequency may reach 15kHz. Similarly,
the output circuit electric current signal also decomposable for only
contains the sine wave the fundamental wave and other each 次谐?
but higher harmonic current to load direct disturbance. Moreover
higher harmonic current also through electric cable to space
radiation, disturbance neighbor electrical equipment. 2. suppressions harmonic interference commonly used
method The overtone dissemination way is the conduction
and the radiation, the solution conducted interference mainly is
filters out in the electric circuit the conduction high-frequency
current or the isolation; The solution radiated interference is
or the line which disturbs is carried on to the radiant the shield.
Specifically commonly used method: (1) the frequency
conversion system electric power supply is mutually independent with
other equipment electric power supplies, or in the frequency changer
and other current collector 输入?the installment insulating
transformer, shuts off the harmonic current. (2) in the
frequency changer 输入?AND output side series connection
appropriate reactor, or installs the harmonic filter, the filter
composition must be LC, the absorption overtone and increases the
power source or the load impedance, achieves the suppression overtone
the goal. (3) between the electric motor and the frequency
changer the electric cable should put on the steel pipe to lay or with
the armored cable, and separately lays with other weak electrical
signals in the different cable trench, avoids the radiated
interference. (4) the holding wire uses the shielded wire, also
when wiring staggers the certain distance with the frequency changer
host return route pilot wire (at least above 20cm), shuts off the
radiated interference. (5) the frequency changer use
special-purpose meets the grounding, also with the thick short line
earth, is close to other electric appliance equipment the grounding to
have to match the line with the frequency changer to separate, use
short line. This can effectively suppress the current harmonics
to be close to the equipment the radiated interference. 3. suppressions harmonic interference example The example 1, some frequency conversion hand-off
control system, the frequency changer starts the movement normally,
but is close to the liquidometer reading to be high, when a table
inputs 4mA, the fluid position demonstration is not under the limiting
value; When fluid position not to hypothesis in limiting value,
the liquidometer actually demonstrates the upper limit, causes the
frequency changer receive engine off instruction, forces the frequency
changer to stop moving. This obviously is the frequency changer higher harmonic
disturbance liquidometer, the disturbance dissemination way is the
liquidometer power source return route or the holding wire.
Solution: Takes the liquidometer electric power supply
from another power supply transformer, the harmonic interference
weakens, again penetrates the holding wire the steel pipe to lay, and
returns to the route with the frequency changer host to separate the
certain distance, after processes like this, the harmonic interference
basic suppression, the liquidometer work restores normally. The example 2, some frequency conversion control fluid
position display system, the liquidometer and the frequency changer in
the identical cabinet body installment, the frequency changer work are
normal, but the liquidometer demonstrated does not permit also is not
steady, at first we cherish congeal a time of table, two tables, the
holding wire and the fluid medium have the question, replacement all
these measuring appliances, the signal electric cable, and the
improvement fluid characteristic, the breakdown still exists, but this
breakdown is the frequency changer higher harmonic current through the
output circuit electric cable to the external radiation, transmits the
signal electric cable, causes the disturbance. Solution: The liquidometer holding wire and its the
pilot wire and the frequency changer pilot wire and the host return
route line separates the certain distance, also the cabinet in vitro
holding wire penetrates the steel pipe to lay, outer covering good
earth, trouble shooting. The example 3, some frequency
conversion control system, is composed by two frequency changers, also
when identical cabinet in vivo, the frequency changer frequency
modulation way for the potentiometer 手调 way, moves some frequency
changer, work normal, when two simultaneously move, the frequency
mutually disturbs, namely adjusts a frequency changer the
potentiometer to be influential to another frequency changer
frequency, in turn is also same. Starts us to think is the
potentiometer and the pilot wire breakdown, after rules out this kind
of possibility, concluded is the harmonic interference causes. Solution: Transfers to other cabinet bodies
potentiometer to be fixed, also the lead wire with shields the holding
wire, the result disturbance weakens. In order to thoroughly
suppresses the disturbance, reprocesses an electrically controlled
cabinet, and with the original cabinet body certain distance laying
aside, transfers to a frequency changer this electrically controlled
cabinet, the corresponding wiring and the lead wire make the essential
modification, after like this processes, disturbance basic
elimination, trouble shooting. The example 4, some frequency
conversion control system, cuts two sets machine to pump, original
machine pumps is depends on falls from the pair presses the start
labor frequency movement to be normal, presently changes the frequency
conversion movement, although can realize the frequency modulation to
decelerate the function, but seriously gives off heat the frequency
changer out-port to electric motor between output line, the electric
motor outer covering 温升 aggravates, frequently appears the
protection to trip. This is because in the frequency changer
output voltage and the electric current signal contains the PWM higher
harmonic, but the harmonic current 绕线on forms the attachment power
loss in the output wire and the electric motor. Solution: Separate the frequency changer input line
and the output line, separately walks respective cable trench, selects
the big section the electric cable to trade the original electric
cable, between the out-port and the electric motor electric cable
length is as far as possible short. After like this processes,
gives off heat trouble shooting. Each kind of frequency changer
higher harmonic disturbance appears which to the scene, basically all
can the method smooth suppression which introduced according to above,
but to the harmonic components and the scope request very strict
equipment, the thorough suppression higher harmonic disturbance is
extremely difficult, waits for further attacks the solution. |