EPS emergency power supply starting with present situation as
well as development tendency 韦德 electronic limited company engineering dept Abstract: Does the emergency power supply EPS
principle of work, how as well as enable the user rational to choose
the product. In article time multianalysis EPS structure and
principle of work as well as belt load operational factor and movement
parameter. Key word: Emergency power supply; EPS;
Emergency power supply principle of work; EPS
characteristic The EPS emergency power supply has been widely
applied to the construction electricity domain and the special
emergency power supply situation. Develops along with the
society, more is the information, the modernization, relies on the
electric power. The sudden power failure inevitably can give the
people the normal life order and the study brings the influence, in
particular regarding in production, life specially important load,
once the severance power supply, will be able to create the
significant economic loss. However, the electric power breakdown
has the burst characteristics, take people's will as the shift, even
if the electrical network facility is again advanced, the accidental
power failure also is unavoidable. At present, the city power
supply system security countermeasure generally uses the incorporation
power supply, provides the reliable power source protection for the
city electric power. But from the enterprise and the industry,
the civil construction service condition looked that, merely depends
on the public electrical network by far to be also insufficient, must
have the emergency power supply system (EPS), the emergency electric
power which its importance is in which the accident has the situation
guarantees provides needs, to effectively reduces the loss which
creates because of the power failure, produces for the people with the
life safely provides the safeguard. Therefore, EPS is also
called "the city lifeline system" important constituent. 1.1 EPS emergency power supply classification At present in the market EPS emergency power
supply brand is multitudinous, everybody the control mode and the
control method which uses in the design 不尽相同, but aims at
brings load the type approximately to be allowed to induce into
following three kinds: One is mainly uses in the emergency
lighting and emergency lighting single-phase EPS is corresponding the
our company the WY series; Two, uses in beside the emergency
lighting, the emergency lighting, but also has applies mix power
supply three-phase series EPS which to air conditioning, the elevator,
the volume curtain gate, the exhaust air blower, the water pump and so
on the inductive load or has both at the same time is corresponding
the our company WYS series; Three is directly corresponding to
electric motor power supply frequency conversion series EPS the our
company WYS/B series. 1.2 EPS emergency power supply design request The EPS emergency power supply may say is a nearly two
year only then swift and violent development emerging industry,
compares says to development mature UPS, has same place, also has
differently place. Its same spot lies in all has (severance) in
the situation continues in the city electricity breakdown to the load
to provide the alternating current supply the function, has used the
IGBT inversion technology and the pulse-duration modulation (PWM) the
technology. Similarity is UPS besides provides the uninterrupted
power supply, but also has both the improvement city electricity
quality the function, but EPS emergency power supply then mainly
solves time the city electricity breakdown emergency power supply
problem; UPS mainly is the IT profession equipment provides uses
electricity the safeguard, the EPS emergency power supply is suitable
for each profession; UPS power supply pattern request cut time
very short (0 ~ 10ms), the EPS emergency power supply then relative is
wider (0 ~ 4s); UPS main belt computer class load, but the EPS
emergency power supply brings the load to be promiscuous; UPS is
higher regarding the movement environment request, the EPS emergency
power supply requests to be able to adapt each kind of environment;
UPS by the common user monitoring primarily, the EPS emergency
power supply mainly uses in emergency to supply power, request and
fire linkage; UPS unimpededly maintains the intelligence
transmission primarily to want the goal, the EPS emergency power
supply to guard against the significant disaster accident primarily to
want the goal. May vividly the analogy, UPS to "rescue the data"
primarily, but EPS to "rescues the person" primarily. The
general EPS power is bigger, machine in inversion is at the readiness
condition. In view of the fact that the EPS emergency power supply main
design thought is when the city electricity sudden stop provides the
safe reliable emergency electric power supply, effectively avoids
having time the disaster person casualties and the property damage is
the principle. Therefore, when designs EPS should emphatically
consider its security, the reliability, the serviceability and the
rationality. Mainly has: 1) the power failure switching time generally in a millisecond
level (25ms), guarantees the power supply timeliness; 2) load adaptiveness strong, including 电容? 电感?
mixed type load, moreover the overload capacity and the anti- impact
ability are strong; 3) has the multichannel output, prevented the output solely
forms breakdown; 4) has the fire linkage and the long-distance control signal,
but manual and automatic interconversion; 5) environment adaptiveness strong, is suitable to each kind of
adverse circumstance, has prevented the high low temperature, is hot
and damp, the salt mist, the dust, the vibration and the mouse nips
and so on the measure; 6) the service life is long, has the battery rapid charge rate
ability and the management ability; 7) conserves energy, operating efficiency high, the movement
cost is low; 8) whether there is does the person value defend, the automatic
operation function; 9) reports to the police the function to be complete, can
promptly provide each kind of unusual condition reporting to the
police; 10) has the strong start function, after avoids the battery link
protection being unable to start; 11) does not have the smog, does not have the noise, does not
have the environmental damage and so on; 12) maintains simply, the maintenance cost is low. 1.3 EPS emergency power supply principle of design 1) the emergency lighting and emergency lighting class
illumination EPS generally take single-phase primarily, mainly as the
emergency lighting situation (market, recreation area, work place,
transaction place and so on) provides the centralism power supply,
like chart 2 shows. When inputs the power source normally, a
city electricity group through switching device output for daily
illumination, another group through battery charger to group charging,
when the controller examines the city electricity severance either
exceptionally (somewhat low or is high), to the inversion sends out
the start signal, and the control mutually throws the switching device
to transfer to the inversion output. Certainly, is different
regarding the EPS connection, but also may treat as EPS two groups
power sources, three groups power sources uses. Chart 2 illuminates the EPS power supply system 2) the emergency lighting and mixed type load 类此
type EPS generally is suitable for the load nature quite complex
situation, for example both has the illumination load, and has the
power load, therefore generally to three-phase is in the majority,
like chart 3 shows. Suitable situation for guesthouse, high-rise
construction, hospital, large-scale market and so on. Chart 3 mix load EPS power supply system 3) the electrical machinery special-purpose frequency
conversion starts 类此 kind of type EPS mainly to design for the
electrical machinery class load, avoids because the electrical
machinery starting in the process the big electric current impact to
damage the equipment. Is widely applied to the high efficiency
electric motor load, for instance elevator, fire pump, large-scale air
blower and so on. Similarity is this kind of EPS generally only
has the single-channel with other EPS to output, like chart 4 shows.
After three-phase loses the enter the market electricity is
normal after the rectification to the inversion provides the direct
current, simultaneously passes through the battery charger to the
group charging; When three-phase input power failure or
exceptionally, from turns provides the direct current by the battery
to the frequency changer. When needs the electrical machinery
load work, gives the frequency changer start signal (movement signal,
long-distance control signal and so on), the frequency changer can
output immediately. From 0 ~ 50Hz frequency conversion, the
supplies electric motor carries on the frequency conversion to start,
after its frequency arrives 50Hz to maintain the normal operation. Chart 4 electrical machinery special-purpose EPS power supply
system 1.4 EPS emergency power supply domain present situation Along with the technical unceasing development, the
multitudinous intelligent building rises straight from the ground, the
people while proposed higher request to its environment, also proposed
the electric power safeguard and the fire prevention security problem.
But the EPS start compares the generator and UPS must be late,
the people are also insufficient to its understanding degree,
therefore in multitudinous emergency power supply situation, or as the
main emergency power supply way realizes the EPS function take the
generator and UPS. Speaking of provides the emergency power
supply ability, these two ways have exposed many deficiency. 1) with the diesel oil power set took the emergency power supply
is, also is the most common emergency emergency power supply which the
present majority of projects uses, because diesel electric engine
capacity bigger, but and machine the movement also the continuously on
time are long, therefore already had the longer application history.
However, regardless of the generator starting rate is much
quick, causes the generator after the power cut to receive the
activating signal to start, to the generator voltage, the frequency
and so on achieved stable may supply power when up to, at least needs
factor ten s to count min, this period of time, all current collector
knock off, possibly creates the minority equipment the damage or
appears the life and property the security problem. But the EPS
start generally cannot surpass 25ms, therefore cannot affect the
equipment the normal work. On the other hand, diesel electric engine application in
emergency power supply situation, some many disadvantageous place,
including: (1) in the high-rise construction, the diesel oil power set
generally puts on the basement, the design difficulty in a big way,
the construction cost is high, provides the wind, cooling, discharges
fume, the absorption of shock, 消音 and so on the facility all needs
fully to consider; (2) has the fire hidden danger. Its oil pot likes
extremely dangerously "the bomb", 11,000 catches fire, the consequence
is inconceivable; (3) routine maintenance quite frequent, the work load is big; (4) the diesel electric engine noise is big, has the
environmental damage; (5) discharges fume has the massive sulphur dioxide, the
pollution is serious, affects the environmental protection. Take the load capacity as 200kW is the example, compares with
EPS and the diesel oil power set's natural price to compare.
When selects EPS, its rated power and the load power ratio are
1: 1 then, its total price approximately is about 600,000 Yuan.
But selects the diesel oil electricity generation machine-hour,
its rated power and the load power ratio should be 1.3 ~ 1.5: 1,
to the 200kW load, the diesel oil power set needs the 250kVA
specification, this unit price is about 400,000 Yuan, but except unit
itself price outside, but also needs the sur- other auxiliary unit
expense approximately 16 ~ 290,000 Yuan, presently take 200,000 Yuan
computations, namely selects the diesel oil power set total price as
about 600,000 Yuan. Therefore, the two price difference are not
many. Is not difficult to see, if the EPS capacity is smaller
than time 200kW, its price must be smaller than the diesel oil power
set's comprehensive construction cost. At present the fire
emergency power supply situation load aggregate capacity generally
below 200kW, considered from the investment long-term benefits that,
EPS compares the diesel oil power set economy many. 2) with UPS took emergency power supply EPS is mostly the same
except for minor differences from the principle structure and UPS.
On-line UPS no matter city electricity is whether normal, it all
continuously by the inversion power supply, namely defers to "the city
electricity input -> rectification -> inversion -> output" the order
carries on, only has when the inversion breakdown or the overload only
then changes by the bypass outputs, like chart 5 shows. But EPS,
when the city electricity is normal, the city electricity gives the
load through the switch S output, simultaneously battery charger to
battery charge. When the control system examines the city
electricity power cut, the inversion work, causes the switch S cut to
the contravariant output condition, provides the electrical energy to
the load, like chart 6 shows. Chart 5 UPS power supply system Chart 6 EPS power supply system Supplies power the diagram from above to be allowed to
see, UPS is one kind of double transformation structure UPS, mainly
provides the stable high grade electrical energy for the load, not
city electricity electrical network influence, moreover its switching
time generally in 10ms, therefore, UPS is widely applied to the
computer, the program controlled switch, the medical equipment and the
precise electronic instrumentation and so on cannot sever the power
supply the place. But just because UPS not only is shouldering
outside the emergency power supply, but also is undertaking the
improvement electric power quality task, therefore its inversion must
continuously unceasingly work, service life relative shorter,
generally is 5 ~ 8 years, the battery replacement is in particular
frequent. On the other hand, the UPS inversion is in for a long
time the work, own loss bigger, moreover for uses the environment
request to be very high, only can put in calculates in the engine room
or the air conditioned room. UPS specially is the IT profession computer class and the
communication class load designs, its load adaptiveness is inferior to
EPS, explains with examples, if emergency supplies power the situation
to include an exchange induction type electric motor kind of
perceptual load, then can have the very big problem in the UPS design
shaping and the use. Because the motor initial firing current
usually is its nominal current 5 ~ 7 time, but UPS overload capacity
standing operating procedure that, When overloads 125%, A kind
is 10min, B kind is 1min, C kind is 30s; Overloads 150% time
10s. If wants UPS to be able to withstand the electric motor
initial firing current the impact ability, the potential essential
increases UPS the rated capacity, this will enlarge the investment
without doubt, but also not necessarily will be able thorough
settlement the problem. Therefore, selects UPS to take the
emergency power supply, the work is already unreliable, but also must
spend the massive funds. 2 UPS/EPS development tendency 2.1 UPS/EPS control technology Middle and small scale UPS/EPS AC/DC and DC/the AC
transformation majority still used the simulation control circuit,
AC/the DC converter control chip majority integrated, use simple, the
work is reliable. DC/the AC converter control has two essential
ways, one kind is the single closed-loop control, another kind is the
double closed-loop control. Former control circuit is simple,
but difficulty with realizes the out-port to short-circuit the
self-recovery. Latter control has the electric current inner rim
and the voltage outer ring, the voltage regulator output for current
regulator assigning, therefore, the limit electric current assigned
the peak-to-peak value also to limit the inversion maximum output
electric current. Presently, the numerical control has become the new UPS/EPS
control technological development the mainstream, the digital
controller has the precision high, antijamming ability strong, is easy
to realize to the UPS examination, the breakdown diagnosis and the
isolation, is easy to realize the remote control telemetering,
realizes many UPS parallel and hotly inserts pulls out, is easy to
realize to the accumulator cell monitoring and the management.
In other words, the computer involvement caused UPS to have the
intellectualization, was allowed to cause its movement at the most
superior condition. 2.1.1 DSP application Uses the digital signal processor (DSP) the digital PWM
technology, is the numerical control technology core, uses in to
guarantee the UPS/EPS output voltage the quality, namely the guarantee
output voltage, the frequency and the output voltage profile satisfies
the technical specification the request. The numerical control
another important function is realizes the UPS/EPS initial
self-checking and movement self-checking, carries on the fail safe and
the failure isolation, this is simulates the controller to be unable
to be competent. As a result of the digital controller
flexibility, enables the UPS controller the hardware electric circuit
to be allowed to standardize, thus simplified the production, the use
and the service, also greatly enhanced the operational reliability. 2.1.2 control circuits entire microprocessor The UPS/EPS electric circuit is composed by the below
several parts: The main circuit, actuates the electric circuit,
the monitoring to demonstrate and to control the protection circuit
and the correspondence contact surface electric circuit.
Monitoring, the demonstration and the control protection circuit
and the correspondence contact surface electric circuit, may simplify
its electric circuit using the digitized design skill, and solves the
original analogy electric circuit to need to adjust, to have warm
floats and parameter adjustment not easy lacking. Uses the
method is: 1) the entire microprocessor carries out the monitoring, the
demonstration and the control protection circuit and the
correspondence contact surface electric circuit function using the
microprocessor; 2) half microprocessor use analogy electric circuit processing
fast feedback protection circuit, but by the processor processing
idling speed feedback, reports to the police, the demonstration and
the correspondence contact surface function. 2.2 accumulator cells technologies The accumulator cell is the UPS/EPS heart, no matter the
UPS/EPS electric circuit is advanced, its performance finally is
decided by its battery, once the battery expires, good UPS/EPS also is
unable to provide the uninterrupted power supply. At present, UPS/EPS generally all uses exempts the maintenance
seal lead-acid battery, because uses the negative pole absorption type
seal technology, overcame the ordinary accumulator cell to need
regularly to make up the water the shortcoming, had "exempts the
maintenance", the easy to operate, does not pollute the environment,
the volume is small, the weight light merit. It uses Gao Qingguo
the electric potential the slab lattice material, reduced the battery
in depositing and the charging-up gas decomposition. The
positive electrode surface superfine glass fiber membrane, prevented
the active material to fall off, enhanced the battery life. The
safety valve use causes the accumulator cell very little to produce
the gas, also may cause the oxygen which produces to absorb by the
cathode lead, causes the accumulator cell anhydrous loss, had achieved
the seal exempts the maintenance the goal. In the ordinary circumstances, affects the battery performance
the primary factor is the trickle charge, the battery trickle charge
approximately must reduce a half service life. At present
overseas uses one kind of ABM (Advanced Battery Management) three stages batteries management plan,
namely the charge divides into three stages: The first stage is
恒流 the equalizing charge, imitates the battery capacity to 90%;
The second stage is the floating charge, imitates the battery
capacity to 100%, then stops charging; The third stage is the
nature electric discharge, in this stage, the battery uses own leakage
to flow the electric discharge, continuously arrives the stipulation
the voltage lower limit, again duplicates the above three stages.
After this way changed before that kind to fill the electricity,
still caused the battery to be at day 24h 浮充 the condition,
therefore lengthened the battery life. The metallized nickel hydrogen battery has the high energy
density the merit, moreover does not have the cadmium pollution which
the nickel cadmium cell possibly creates, applies it to UPS/EPS may
receive the small 轻量 merit. But its shortcoming is the
selling price too is high. American Alupower Corporation
researches and develops the power lead - air emergency power unit
(RPU), movement >= 50h, the power from 600W to 6000W, the voltage has
DC24V and the 48V two kinds, its energy density is plumbous acid
battery more than ten times, the weight only has the plumbous acid
battery 1/10, occupies the space only to have the plumbous acid
battery 1/7, hopefully substitutes for the lead-acid battery to apply
to UPS/EPS. 3.3 EPS emergency power supply development tendency Because EPS brings the load type the complexity and the
environment relative constancy, in view of the different situation,
the different load, may do to the EPS function draws close to the
reality application. Including following several aspects. 1) structure composition ordinary EPS in order to unifies the
practical application well, often uses "gathers one" the structural
design, but as a result of load and environment complexity, also from
this brings the equipment standardization and the design institute,
the user shaping difficulty. Solution uses the modular design,
separates the main engine and the input or the output power
distribution. The main engine module completes the main energy
conversion and the communication control function; Power
distribution module realization rich power distribution management
function. The main engine module through the standard control
connection realization to the power distribution module management,
like the double power source automatic cut over function, the multi-
return routes output function, the fire linkage function should
realize in the power distribution module. 2) the power distribution module should increase function EPS to
use in the urgent load power supply, its load often for non- sole
load, but these loads 不尽相同 in the emergency case essential
degree, therefore, said regarding EPS, certain power distribution
management functions are very important. (1) the smooth start function such as, the EPS load very major
part is the perception shock load, has the bigger starting current,
when shaping must enlarge the EPS capacity, thus creates the equipment
resources the waste as well as the user cost increase. In fact,
as a result of the EPS load power supply may the discontinuity, EPS be
possible to increase 8 groups or 16 group programmable power
distribution management connection, through the order, the time which
starts to the load carry on the control, may solve the start surge
current in the very great degree and enlarge the shaping capacity the
question. (2) the partial unloading function decided by the EPS load
nature, when overloads occurs, needs EPS as far as possible to
continue to work, but cannot look like UPS such to carry on protection
closing machine, therefore, similarly passable power distribution
management connection dismantle secondary load. 3) battery management because the EPS use environment generally
compares UPS to be bad below, for lengthens the accumulator cell as
far as possible the service life, the battery charger should
simultaneously have the function: (1) may establish the charge to limit the class; (2) may establish the battery discharge final voltage; (3) has the automatic 浮充 function, the charge mechanism
should conform to the DIN41773 standard; (4) has 浮充 the voltage temperature compensation function; (5) intelligent battery examination function; (6) the deep electric discharge protection (may force
emergency). 4) the frequency conversion starting function at present the
frequency conversion starting EPS design, like chart 8 shows, mainly
focuses to a solution bigger electric motor, like load and so on
elevator, water pump, air blower starting impact question, but a more
reasonable design, should be on-line UPS and the frequency changer
technology perfect union. On-line UPS has the mature
rectification, the battery management technology; The frequency
changer has the mature frequency conversion control technology, two
organic synthesis are this application domain ultimate development
directions. Chart 8 frequency conversion starting Conclusion Along with society's progress and the development, the
environment request unceasing enhancement, fire consciousness more and
more is also taken by the people. EPS is known by its unique
superiority by the people with the use, in a project, it may the
nimble utilization in the fire power supply return route terminal, the
individual important situation and so on the many kinds of situations.
On the choice emergency power supply, no longer only limited to
the diesel electric engine, because they respective characteristic
separately was suitable for the different project, this will provide a
more powerful safeguard for the entire society's security. Reference 1 "Civil construction Electricity Design Standard"
Chinese plan publishing house,1,993 2 GB17945-2000 country standard (fire