RS-485 main line theory and utilization
Origin: Input time: 07-06-10 01:42:39English version

This article introduced the RS-485 main line theory, the RS-485 main line system the question which exists in the data communication process, as well as in RS-485 actual project application.
1st, outline
Along with the digital technology development and the computer widespread application, now a system often is composed day by day by many computers, needs to solve the multi- stations, the remote communication question. When the request signal distance is several dozens meters to on kilometer, widely uses the RS-485 transceiver. The RS-485 transceiver uses the balance transmission and the difference receive, therefore has the ability which the suppression altogether mold disturbs, in addition the receiver has the high sensitivity, can examine lowly reaches 200mV the voltage, therefore the transmission signal can obtain the restoration outside the kilometer. Uses the RS-485 main line, a pair of twisted pair line can realize the multi- stations networking, constituted the distributional system, the equipment simple, the price is inexpensive, can carry on the long distance correspondence the merit enable it to obtain the widespread application
2nd, RS-485 main line theory
In the automated domain, along with the distributional control system development, the urgent need one kind of main line can suit the long-distance range the digital communication. In in the RS-422 standard foundation, EIA studied one kind to support the multi- pitch points, the long-distance range and receives the high sensitivity the RS-485 main line standard.
The RS-485 standard picks the useful balance -like transmission, the bad fraction receive data transceiver actuates the main line, concrete specification requirement:
Receiver input resistance RIN >= 12k Omega
The driver can output ±7V altogether mold voltage
Input end electric capacity <= 50pF
In the festival points is 32, has disposed in 120 Omega terminals resistances situation, the driver at least also can output voltage 1.5V (terminal resistance size with use twisted pair line related parameter)
The receiver input sensitivity is 200mV (namely (V+) - (V-) >= 0.2V, indicates signal "0"; (V+) - (V-) <= -0.2V, indicates signal "1")
Because of the RS-485 long-distance range, the multi- pitch points (32) as well as the transmission line cost low characteristic, enables EIA RS-485 to become in the industrial application the data transmission first choice standard. Based on this, RS-485 automated domain application extremely widespread, but the RS-485 main line utilization still has very many problems in the actual project, has affected the project quality, brought for the project construction have been very many is not convenient.
1st, impedance not continuously
Signal in transmission process if meets the impedance to change suddenly, the signal can cause the reflection in this place, this kind of signalling principle, enters another kind of medium with the light from one kind of medium to have to cause the reflection is similar. Eliminates this kind of reflection the method, is maintains the transmission line impedance to be continual as far as possible, in the actual project bridges in the electric cable line terminal is for reduce the signalling with the electric cable characteristic impedance similar size terminal resistance principle.
Theoretically analyzes, is transmitting the electric cable terminal so long as has bridged the terminal resistance which matches with the electric cable characteristic impedance, can the effective reduction signalling. But, in realization application, because transmits application environment and so on electric cable characteristic impedance and communication baud rate related, the characteristic impedance is impossible and the terminal resistance closely coincide, therefore the more or less signalling also can exist. The signalling logarithm according to the transmission influence, is in the final analysis because the reflection signal has triggered the receiver input end comparator, caused the receiver to receive the wrong signal, caused CRC to verify the mistake or the entire data frame is wrong. This kind of situation is unable to change, only has avoids it as far as possible.
2nd, RS-485 earth question
Merely uses a pair of twisted pair line each connection A, the B end connection to get up, but to the RS-485 correspondence link signal ground, also may not work in certain situations, but buried the hidden danger to the system. The RS-485 connection uses the difference way transmission signal certainly not to need to examine the signalling system regarding some reference point, only had to examine two between the potential difference to be allowed. But should pay attention is the transceiver only has under altogether the mold voltage does not surpass the certain scope (-7V to +12V) the condition can the normal work. When altogether the mold voltage surpasses this scope, can affect the correspondence to be reliable until the damage connection. Like chart 1 shows, when transmitter A to receiver B transmission data, the transmitter A output altogether mold voltage is VOS, because two systems have each one independent earth system to have terrestrial electricity potential difference VGPD, then the receiver input end altogether the mold voltage can achieve VCM=VOS+VGPD. RS-485 standing operating procedure VOS <= 3V, but VGPD possibly can very large scale have (several volts even dozens of volts), and the possible partner to have 强干?the signal to cause the receiver altogether mold to input VCM to surpass normally encircles, lightly produces the interference current on the holding wire to affect the normal correspondence, heavy piece of damage equipment.

According to this in new window browsing picture
3rd, RS-485 main line structure and transmitting range
RS-485 supports the half-duplex or entire duplex pattern. The network analysis situs generally uses the terminal match the main line structure not to support ring-like or the star network, best uses a main line to serially connect each pitch point. From the main line to each pitch point lead-out wire length should as far as possible short, in order to causes in the lead-out wire the reflection signal to be lowest to the main line signal influence. When uses the RS485 connection, passes through regarding the specific transmission line, from the generator the biggest electric cable length which permits to the load its data signalling is the data signal speed function, this length data mainly is influence and so on signal distortion and noise limits. When the data signal speed reduces to 90Kbit/S below, when the hypothesis biggest permission signal loss is 6dBV, then the electric cable length is limited in 1200M. In fact, when is practical is definitely may obtain compared to its big electric cable length. When uses the different line diameter the electric cable. Then obtains the biggest electric cable length is not same.
3 plans designs
Below explains RS-485 by an example the application:
A university cafeteria has three, some 12 POS machine, each building has 4 POS machine, they are the RS-485 connection, controls the POS machine computer to meet the RS-232 connection, the traditional solution is:

According to this in new window browsing picture
Uses this kind of old style wiring structure to have following several kind of flaws.
1>, the RS-485 main line the difference signalling characteristic limit main line length about 1,200 meters, is generally used this kind of old style wiring structure, but the wiring cover area extremely is limited (generally is several hundred square meters). Sometimes in order to open up the transmitting range to be able not but to use the repeater. Simultaneously also enlarged in the wiring process to have the problem the possibility.
2>, the general large-scale checking attendance 门禁 system all is loaded with for the number multitudinous 门禁 controller, uses this kind of old style wiring structure, all 门禁 controllers sharing identical root RS-485 main line. When any controller RS-485 port short-circuits, can affect the entire 门禁 system the normal work. Searches the breakdown in the multitudinous 门禁 controller to be at, not only has enlarged the work load, also increased the maintenance cost.
3>, because the RS-485 main line wiring quite is complex, the major part project expense and the time all wastes in the checking attendance 门禁 system in the wiring link. But the RS-485 main line wiring complex degree and the main line length and the equipment hang meets the number to have the very big relations. Specially appears in the large-scale system by for is prominent. Used this kind of old style wiring structure to increase the wiring difficulty without doubt.
4>, as a result of the geographical environment reason, in is distanced between the certain distance equipment always to have the electric potential not balanced problem. Sometimes even if is away from the very near question still to exist. This kind of environment creates factor, in old style wiring structure very difficult comprehensive solution. Even creates the overall system to be unable to start. Although may temporarily solve the partial problems through the processing electric potential, but 时隔不久 the similar question can appear once more.
Some flaws appears which in view of above, the trillion Vietnamese company develops a section new product, it uses unique and so on the rank difference isolation technology and the highly effective main line division centralism technology can in the effective addressing project wiring the common terrestrial electricity position difference, the impedance matching and is struck by lightning the question. The user may easily improve the RS-485/RS-422 main line structure, the division webpage, enhances the correspondence reliability. When is struck by lightning or the equipment failure produces, has the problem the webpage to isolate, guarantees other webpages the normal work. Again solution as follows:

According to this in new window browsing picture

May the effective solution use the first kind of plan existence using this plan the flaw, it has the following several advantage:
1>, uses the star structure to connect the RS-485 main line, the wiring cover area greatly enhances in the effective use connection situation (generally is several square kilometers).
2>, has eight lower positions machine ports, also each port all has short-circuits the protection function, and can work is shutting off the pattern. To the large-scale checking attendance 门禁 system, through shares 门禁 the controller not only to be allowed to reduce individually the RS-485 main line load to eight ports, simultaneously effective enhancement overall system reliability. When any controller RS-485 port short-circuits, only can affect its in the RS-485 main line system, cannot affect other connection connections the RS-485 system normal work.
3>, may cause the RS-485 system wiring process to change simple and quick is clean, thus effective reduced project expense and time.
Between 4>, various ports has the 3000V isolation. Regarding wiring question which brings by the environment question, only must carry on the question remarkable region with the independent port connection centralism processing, will be able the effective solution electric potential to bring wiring question.
4th, matters needing attention
4.1 very many people often all mistake are the RS-422 serial interface are the RS-485 serial interface entire duplex editions, in fact, they have many differences in the electric appliance characteristic, altogether the mold voltage scope and the receiver input resistance differently cause this two standards to be suitable for the different application domain. The RS-485 serial interface driver may use in the RS-422 serial interface application, because the RS-485 serial interface satisfies all RS-422 serial interface performance parameter, otherwise cannot establish. Regarding the RS-485 serial interface driver, altogether the mold voltage output scope is between -7V and +12V; Regarding the RS-422 serial interface driver, this performance index only has ±7V. The RS-422 serial interface receiver smallest input resistance is 4K Omega; But the RS-485 serial interface receiver smallest input resistance is 12K Omega.
4.2 RS-485 main line always appears some wiring in the actual project the question, the attention, when meets the transmission line certainly must use the same twisted pair line or the same electric cable, a some people of section of use twisted pair line, because the twisted pair line length is insufficient or in on center indirect section of telephone lines or is other lines, such impedance not continuously, produces the very big reflection signal, the correspondence is cannot normally carry on.
5th, concluding remark
The RS-485 main line, has high characteristic and so on noise abatement, width altogether mold scope, long transmitting range, conflict protection, but also needs to consider the reasonable application and the network layout, the continual signal channel, the complete protective measures and so on, should have the overall plan at the beginning of the design. Along with the optical fiber communications ofc and the ethernet technology development, the RS-485 main line data transmission distance can be farther.
Chief-editor: Article author:

In data increase......

Hot spot article
DOM electron hard disk application plan
The MOXA entire series product provides the solution for the highway intelligence transportation
Chinese mugwort news science and technology ?seam profession solution
The prestige reaches the electrician to control the product in the network test facility application
Grinds the auspicious product in the medical profession application
North China branch mechanic controlling machine in hydroelectric power plant strobe control system application
Flies thinks the Cull software solution support automobile micro controller (MCU) the fast prototype development
Grinds auspicious labor controlling machine in the ATM profession solution
The transportation information broadcasts the newspaper solution
Grinds raises PCM-3336 in the multi- parameters medical monitoring meter application
In data increase......
Website map
Copyright 2006-2008