> Will synthesize the wiring system to take the
construction intellectualization essential infrastructure, its earth
system quality directly will affect the synthesis wiring system
movement quality, therefore will appear especially importantly.
This article in detail introduced the synthesis wiring system
earth the structure and the design request, and proposed should pay
attention to several items in the earth design. According to commercial building earth and wiring request
stipulation that, The comprehensive wiring system earth
structure including meets the grounding, the ground strap (level earth
terminal), the earth skeleton line. Host ground strap (total
earth terminal). The earth directs the inlet, to meet the
terrain six parts, when carries on the system earth the design, may
carry on the design in administrative levels according to the above 6
essential factors. 1. meets the grounding Meets the grounding is refers to synthesis wiring
system each kind of equipment and between the ground strap segment.
All meets the grounding for the copper nature insulated
conductor, its section should not be smaller than 4mm2. When
the synthesis wiring system uses the shielded cable wiring, the
information plug earth may meet grounding from Lian Zhimei using the
cable shielding level achievement the level to match the line cabinet.
When the synthesis wiring electric cable uses puts on the steel
pipe or the metal line badly lays, the steel pipe or the metal line
are bad should maintain the continual electrical connection, and
should have the good earth in the beginnings and ends. 2. ground straps (level earth terminal) The ground strap is the horizontal wiring meets
the grounding to the system the public central junction. Each
floor matches the line cabinet to be supposed to weld with this floor
ground strap with the ground strap identical matches the metal which
the space all syntheses wiring uses and the earth skeleton line should
with this ground strap weld. The ground strap should be the
copper generatrix, its most light-sized should be the 6mm thick ×50mm
width, the length regards the project actual need to determine.
The ground strap should use the electrotinning to reduce the
contact resistance as far as possible, if is not the galvanization,
then in fixes the wire to the generatrix in front of, must carry on
the cleaning up to the generatrix. 3. earths skeleton lines The earth skeleton line is draws out by the total
ground strap, connection all ground strap earth lead. When
carries on the earth skeleton line the design, should fully consider
the building the structural style, the building size as well as the
synthesis wiring route and the spatial disposition, and lays with the
synthesis wiring electric cable skeleton line coordinates. The
earth skeleton line should install in not physical and the mechanical
damage protection place, in the building water pipe and the metal
cable shielding level cannot take the earth skeleton line use.
When in the building uses two or many vertical earths skeleton
lines, between the vertical earth skeleton line each three and the top
layer must with with earth the skeleton line constant section
insulated conductor to weld. The earth skeleton line should for
insulate the copper core wire, the smallest section should not be
smaller than 16mm2. When when the earth skeleton line, its
differential earth potentials is bigger than 1Vrm@S (有效?, the
floor matches the space to be supposed alone to use the earth skeleton
line to meet to the host ground strap. 4. hosts ground strap (total earth terminal) In the ordinary circumstances, each building has a
host ground strap. The host ground strap took in the synthesis
wiring earth system earths the skeleton line and the equipment meets
the grounding the extension contact, its ideal position suitably
supposes to the outwire introduction once in a while constructs
matches the space. The host ground strap should arrange in the
straight line way, simultaneously considered does not proclaim from
the protector to the host ground strap welding wire excessively long.
The earth directs the inlet, the earth skeleton line, direct
current 配电?to meet the grounding, the outwire introduction all
meets the grounding, as well as identical matches metal with the host
ground strap which the space all syntheses wiring uses to be supposed
and the host ground strap good welding. When the outwire
entrance cable has the shield or puts on the metal 保护? this
shield and the metal tube also should weld to the host ground strap.
The host ground strap should use the copper generatrix, its
smallest section size is 6mm the thick X100mm width, the length
visible project actual need decides. Is same with the ground
strap, advocates the ground strap also to be supposed to use the
electrotinning to reduce the contact resistance as far as possible.
If is not the galvanization, then the host ground strap in fixes
must carry on the cleaning up to the wire in front of. 5. earths directs the inlet The earth directs the inlet to refer to the host
ground strap with to meet between the terrain the ties, suitably uses
the 40mm width ×4mm is thick or 50mm×5mm galvanizes the flat steel.
The earth directs the inlet to be supposed to make the
insulation antiseptic treatment, should have in its unearthed spot
guards against the mechanical damage measure, also not suitably puts
with the warm air pipeline with the ditch cloth. 6. meets the terrain Meets the terrain to divide the nature to meet the
terrain and artificially to meet the terrain two kinds. When the
synthesis wiring uses the alone earth system, meets the terrain
generally to use artificially meets the terrain below, and should
satisfy the condition: (1) meets the terrain from the labor frequency low
pressure exchange power supply system not to proclaim is smaller than
10m. (2) meets the terrain from the building anti-radar system
not to be supposed to be smaller than 2m. (3) the earth resistance should not be bigger than 40
Omega. When the synthesis wiring uses the union earth system,
meets in the terrain general use building foundation 钢筋?to meet
the terrain as the nature, its earth resistance should be smaller than
1 Omega. Usually uses the union earth system in the practical
application, this is because compares with former, the union earth way
has following several remarkable merits: (1) when the building suffers is struck by lightning, in
the floor each potential distribution quite is even, the staff and the
equipment peaceful versatilely obtains a better safeguard. At
the same time, the building portal frame construction provides 10 ~
40dB to the center wave electromagnetism field energy the shield
effect. (2) is easy to obtain the smaller earth resistance. (3) may save the metal material, 占地 are few. Carries on several questions which the synthesis wiring
system the earth design should pay attention When 1. syntheses cities line system uses the
shield measure, all shields level should maintain the continuity, and
should pay attention to between the guarantee wire the relative
position to be invariable. The shield level commutation
equipment (FD or BD) the end receives, the user (terminal device)
looks carefully the special details directly, beginnings and ends
earth: Should connect as far as possible to identically meets
the terrain. When in the earth system has two, when different
meets the terrain, its differential earth potentials should not be
bigger than 1Vr.m.S (有效?. 2. when the electric cable enters the building interior
from the building to be easy to receive is struck by lightning, when
power source 碰地, power source induced e m f or earth potential
上浮 substandard factor influence, must use the protector. Below 3. when the line is in any kind of dangerous
environment, should carry on to it has pressed has flowed the
protection: (1) is struck by lightning the dangerous influence which
causes. (2) the working voltage surpasses 250V the power source
line 碰地; (3) the earth potential rises the power failure which
causes to 250V above; (4) exchanges the 50HZ induced tension to surpass 250V. 4. syntheses wiring system 过压保护 suitably selects
the gaseous tube protector. Because in the gaseous tube
protector ceramic outer covering seals has two electrodes, during has
the electric discharge gap, and sufficiently has the inert gas.
When between two electrodes potential differences surpass the
250V alternating voltage or the 700V thunder and lightning surge
voltage, the gaseous tube starts to appear the electric arc, and
地电?between has provided a conductive path for the conductor. 5. syntheses wiring system the class has protected
suitably selects can from the duplicate protector. Because on
the electric cable possibly appears like this or such voltage, if the
interconnection equipment has provided for it to the place low
resistivity circuit, then is insufficient to cause 过压保护 the
movement, but it produces the electric current actually possibly
damages the equipment or causes the fire. Example: The 20V
electricity line of force is possibly insufficient to cause
过压保护 the electric discharge, but has the possibility to have
the big electric current input media interior to create the
destruction, therefore while uses 过压保护 must use has flowed the
protection. The request uses can from duplicate flow the
protector, mainly is for the convenience maintenance. In brief, along with intelligent construction unceasing
development, the people will certainly to its earth system to set a
stricter request. Will say regarding the general engineers and
technicians, enhances the synthesis wiring earth system the stability
and the reliability will be an item long-term and the arduous duty.
The road is endless its 修远 about, we need seek. |