In the production process surveillance and the control needs to use the many kinds of automated measuring appliance, the computer and the corresponding implementing agency, mutually transmits both has the weak millivolt level small signal, and has dozens of volt big signal, even also has reaches as high as several kilovolts, several hundred ampere signals. Says from the frequency, has direct current low frequency, also has the high frequency pulse. Mutual disturbance between the equipment, the measuring appliance of becomes the question which in the system debugging must have to solve. Besides the electromagnetic screen, solves each kind of equipment, the measuring appliance "", namely the signal reference point potential difference, is the scene debugging important question.

    1. isolation two principles

The signal wants the integrity transmission, must solve the different equipment, reference point potential difference between the measuring appliance signal. The idealized situation is all equipment, the measuring appliance signal has a common reference point, namely altogether has "". Further says, all equipment, between the measuring appliance electricity reference point the potential difference is "zero". In the actual environment, this point is nearly impossible. Inside this the loss of voltage which besides each equipment, the measuring appliance "" the between segment resistance produces, still had each kind of equipment, the measuring appliance the disturbance which received in the different environment is different, as well as the wire contact underwent 风吹雨淋, caused the contact quality drop and so on many factors, caused each "" between to have the difference. Take the chart one as the example

According to this in new window browsing picture
Chart PLC meets the measuring appliance schematic drawing with outside

Chart center two scenes equipment 1 #, 2 # to the PLC transmission signal as well as PLC to two scenes equipment 3 #, 4 # send out the signal. Supposes the transmission signal is 0-10VDC. Ideal situation, PLC and two scenes equipment 1 #, 2 # "" electric potential closely coincide. In the transmission process has not disturbed, PLC receives correctly. But 如前所, two scenes equipment usually have "" the potential difference Gives an example to say, 1# equipment "" and PLC "" electric potential same, the 2# equipment electric potential reference point "" electric potential is higher than 0.1V them. Such 1# equipment for the PLC signal is 0-10V, but the 2# equipment for PLC was 0.1V-10.1V, the error produces. Simultaneously 1# the,2# equipment "" the line in the PLC convergence joint, exerts the 0.1V voltage in the PLC line, has the possibility to damage the PLC local circuit board line, simultaneously can demonstrate the wrong data.

"" Causes the question repeatedly has the appearance in the scene debugging. For example some large-scale building materials company in the production line monitoring equipment, has used overseas some company PLC and domestic some factory holding. This PLC each data acquisition board is composed by eight channels, eight channels altogether use 12 A/D, after the process transformation digital signal to transport to isolate by 12 light pairs constitution disconnector realization and the main engine, but between its eight channels input has not certainly isolated. When input signal, each channel alone inputs to the gathering board is normal. When simultaneously inputs two or are many to two exterior signals, demonstrated the numeral jumps madly, the breakdown is unable to remove. Also like astronautics some department uses K 热偶 to take sensor test engine each temperature, with above similar, when tests a spot all normal, when turns on two spots to the main engine or more spots, the demonstration temperature obvious is wrong. After these two kind of situations use disconnector, the question solution work is normal.

The disconnector therefore can play this role, is because it has causes the input/output the characteristic which completely isolates on the electricity. 换句话讲, between the input/output "", the external signal no matter is 0-10V not together, or is bringing altogether mold disturbing voltage 0-10V after the isolation is 0-10V. After namely the isolation the new establishment "" with the external instrumentation, the measuring appliance "" has not related. Is precisely as a result of this reason, also realized has input meets between the equipment measuring appliance signal to outside PLC main engine many to isolate, namely between them did not have "" relations.

On spoke face-to-face the input signal and the PLC isolation, same PLC also has the similar phenomenon question to the external instrumentation output signal, uses the disconnector to be able to achieve solves the question goal.

Another kind frequently meets the situation is requests a signal both to be able to demonstrate the measuring appliance transports the signal, and can transmit for such as the frequency changer and so on equipment, like this has the possibility to produce between two equipment 互扰. By now requested between two outputs also was the isolation. Recommendation use 隔离?signal distributor. It can realize the input signal to isolate with the external instrumentation, simultaneously realizes between the receive signal device to isolate. Like chart 2.

According to this in new window browsing picture
                      
Chart two 隔离?signal distributors model application


In summary, the solution "" the question needs to follow two principles. First: The external instrumentation and the central processing system (for example PLC, DCS) between must carry on the electricity to isolate. Second: External instrumentation signal (regardless of is to central processing system transmission signal external instrumentation to or receive signal external instrumentation) between must realize the mutual electrical isolation. The system installment followed these two principles to be able completely to overcome because "" between difference introduction disturbance.

The majority disconnector all wants the sur- work power source, generally is DC 24V or AC 220V. This power source when for input, output part power supply must guarantee on the electricity/outputs two modified quarantines with the input. Between this kind of input/output/sur- work power source completely mutually isolates the component is called three isolation or all isolates the component. Theoretically speaking, this power supply way no matter disconnector quantity how many, may use a power source power supply, cannot introduce the disturbance. Such product conforms to the above two principles.

    2. bases connections choice product

The industry scene most common signal is 4-20mA□p0-10V, regarding such as physical quantity and so on pressure, temperature, current capacity also must process 4-20mA□p0-10V the signal in order to computer processing. Transforms these physical quantities for the measuring appliance is called with 4-20mA□p0-10V the signal equipment -- changes delivering. The chart three has produced as the sensor isolation temperature changes the delivering application continually graph take Pt100. It manifests the temperature change by the resistance change, thus the scene ties line resistance can introduce the error. Generally says looks like WS9050□pWS2050 this kind to change delivering all to have the long-line compensatory function, can eliminate the lead wire resistance introduction the error and has the linearized function, guarantees the precise transformation.
Looks like WS2050 this kind of two-wire system to change delivering, its power source AND output altogether "", has not isolated. When many Pt100 transports by way of multichannel WS2050 to PLC, although outputs altogether uses a 24V power source, so long as outputs receives has the common reference point the simulation quantity input board, this kind of connection conforms to two principles which this article above pointed out, solved has been different "" the introduction perturbation. Needs to pay attention: Multichannel WS2050 receives different PLC to have to use respective 24V power source.

According to this in new window browsing picture
In view of changes the delivering isolation also to have another way, the sensor and changes delivering is a body but also must lay aside in the scene assigned location. This time generally places the disconnector in the master control room cabinet, changes delivering by the cabinet in disconnector for the scene to match delivers the power source. The chart four has produced in view of the different connection two kind of products continually graph. Which one kind uses to have to decide according to the scene situation.


The scene debugging also can appear the measuring appliance connection not to match. For example the scene transmitter installation for 四线?changes delivering output 4-20mA, but the receiving end 4-20mA connection is two return routes power supplies way, if directly will connect creates the power source conflict. The solution is uses the disconnector the 4-20mA receive and the isolation which comes the scene, installs a allocated-use circuit in the disconnector output part to use to match the connection two return routes power supplies way. This kind of disconnector also may process from scene 0-10V, voltage electric current signal and so on 0-5AAC.

Outside the general 4-20mA electric current signal disconnector needs to meet the work power source. Here recommends one kind not to need other to add the power source again disconnector WS1562. Like chart six

According to this in new window browsing picture
The WS1562 most major characteristic is does not need the external power supply, the wiring simple and direct □p power loss low □p reliable performance is high, the multichannel connection conforms to the above two principles.

According to this in new window browsing picture
The chart seven is WS1562 in the output is under the 20mA condition, output load and input end voltage relations curve. VIN expresses in the input end voltage □pRL expression output load resistor □pVO expression output load resistor voltage.

The chart eight produces two kind of passive disconnectors output load to a linear curve, solid line description performance is better, output load resistor RL from 0 Omega -500 Omega change, linear all in 0.2%.

    3. main parameters selections

The choice disconnector besides must around determine the function □p attention adapts the end connection, still had the precision □p power loss □p noise □p insulation strength □p main line communication function and so on many parameters cautious to need the user to elect.

The precision is the count for much parameter. Are very many with its related department's parameter. The time drifting and the temperature drifted two parameters to indicate the precision stable degree, slightly requested these two parameter values to be better.

Another has the influence parameter to the precision is a noise. Because the disconnector generally uses DC/DC to produce isolates the power source for the product internal circuit power supply, but the input signal also must first modulate the pulse (light occasionally transformer) then to demodulate again after the isolation belt the output. As the core disconnector also has the pulse signal take CPU. These work pulses frequencies 率多 in 20KHZ ~ 100KHZ scope. Its edge steep □p overtone rich, is very difficult to the signal pollution to eliminate. If noise higher, the data acquisition gathering signal error is big. Therefore the noise peak value and the energy smaller are better.

The electrical energy which the power loss is refers to when disconnector work consumes, it involves the quantity of heat which produces to the product. This parameter and the product long-term use reliability has the close relation.

According to the analogous circuit test, the different power loss the quantity of heat which produces in the product shell different, causes in the shell 温升 to be also different. The product is at under the active status, in the product shell compares outside the shell the ambient temperature to have to outdo 10 ?~ 30 ? If radiates is not good, possibly elevates 50 ?above. If shell in vivo hyperpyrexia, composition product primary device in high temperature long lasting work, this can have the important influence to the product performance. The long time high temperature environment causes the operational amplifier parameter transformation □p resistance resistance number change □p electric capacity leakage to increase and so on, this will cause the product performance to drop, even will cause the product expiration. Therefore the user must pay attention to power loss this parameter in the selection, especially bigger □p installs when the amount used a density higher □p radiation is not good, power loss this parameter especially reveals importantly.

The isolation 端子 design miniaturizes day by day, then the miniaturized goal little occupies the space, should allow the user crowdedly to install, crowded installment on existence radiation question. 换句话讲, must reduce the product power loss, reduces the product interior temperature, this enhances one of product reliable premises.
   The majority of disconnectors use the guide rail installment, the wiring use 端子 the wiring, this kind of disconnector usually is called the isolation 端子, is suitable installs in the cabinet, its wiring opens trades conveniently.
 

Information origin: Shanghai Qi Pu electron science and technology limited company
Chief-editor: Article author:

In data increase......

Hot spot article
Based on GPRS long-distance automatic rainfall monitor network
Frequency changer capacity rating and choice
Optical fiber diffraction grating 传感 system present situation and development tendency
The electric power communications network new pattern --- turns on the plan based on the industry ethernet platform synthesis
Automated software designs the IEC 61131-3 standard topic (1)
Uses in to control and the monitor line cable position transmitter
Howchooses the humidity sensor
Field bus type and standard
Howdoes the sensor carry on the passive calibration and two specially explained
Information impetus industrialization: Discussion and practice
In data increase......
Website map
Copyright 2006-2008