The synchronous motor frequency conversion starts the typical breakdown
Origin: Input time: 07-05-10 12:40:03English version


     1  introduction
     
     The synchronous motor by the power factor and the output torque which its may move to the electrical network voltage undulation is insensitive and so on the good performance characteristic to monopolize the chela head in the high efficiency electricity transmission domain, is the actuation large-scale air blower, the water pump, the compressor first choice type. But the large-scale synchronous motor starting is a quite complex question. If starts with the reduced pressure, not only needs the very big transformer, the electrical machinery structure is relatively complex, also the starting has a bigger impact to the electrical network. But uses the load 换相 synchronous motor the principle, carries on the frequency conversion to the large-scale synchronous motor to start, is the quite ideal method. This article three agglutinates the host platoon air blower firing set take the Baoshan Steel Corporation as an example, introduced the synchronous motor frequency conversion starts principle, process as well as typical breakdown and processing method.
     
     2  firing sets basic composition and main parameter
                        
     The Baoshan Steel Corporation three issues agglutinated in 1998 complete go into production, two hosts exhausts air blower electric installation provided by Rolls-Royce Corporation. 
                        
     2.1 firing sets characteristic
     (1) does not have the jigger equipment, true realization static starting; 
     (2) uses not brushes the excitation, maintains the overhaul to be convenient;
     (3) the numerical control system, the debugging was convenient, enhanced the system reliability;
     (4) the electric motor in the in-step condition incorporation, to the motor, the electrical network impact is small.
     
     2.2 main circuits structures
     
     The main return route by falls presses the transformer, three-phase all controls the bridge levelling circuit, the direct current reactor, the crystal thyratron inversion, rises to press the transformer and the synchronous motor is composed. Rectifier control system for speed, electric current negative feedback double closed-loop system; The inversion control system (OPE) and is indirect -like (OPS) by the photoelectricity encoder the rotor position sensor, uses in to throw the net to control 整步 the trimming and the synchronized incorporation. System basic constitution like chart 1 shows. 

                        
     2.3 hosts return routes partial main equipment parameter
                        
     Main return route partial main equipment parameter like table 1 shows.

    According to this in new window browsing picture
According to this in new window browsing picture
  Attempts the 17800kW synchronous machine firing set principle


     Direct current reactor (DC-L) the function is 脉动?limits rectified output direct current under the certain value, guaranteed the inversion work is stable. Considered the crystal thyratron the breakdown voltage and the nominal current, the system used has fallen presses the transformer, rises to press the transformer. Because the variable current return route voltage rank reduces, caused the rectification, to invert each 桥臂 has only used a crystal thyratron.
                        
     3  startings processes
                        
     Sends out the starting from the starting instruction to finish the synchronized incorporation, experienced has risen the pressure to change the bypass - to put through the cut, "forced (off and on) - the nature 换相" the cut, 整步 process and so on trimming and synchronized incorporation, during had 3 times of electric currents limits value cut.
                        
     After sends out the starting instruction, first invests the excitation, then closes the firing set the input, the power take-off valve, causes its investment movement, starts to start. Table in 2 demonstrations startings acceleration process, control mode and main condition change.
                        
     Table in 2 startings acceleration process, control mode and main condition change

According to this in new window browsing picture

                         
      Because the transformer is lower in the low frequency effectiveness for a period of time rate, is insufficient to drive the electric motor, the synchronous motor from when static starts the starting, rises to press the transformer to be at the bypass condition, until the rated speed 8% (4Hz), separates the by-pass switch, puts through rises to press the transformer. When the rotational speed promotes to 10% (5Hz), the electric current restriction from 20% cuts to 50%. This period is uses forces to trade the physiognomy, blocks the flow when 延迟?alpha advances the rectification side 135°, simultaneously leads passes the after flow crystal thyratron, thus as for does not affect inversion blocking the flow because of the reactor energy liberation, fast shuts off the main return route to block the flow, then when reduces alpha angle, the input current starts the increase, reactor beginnings and ends polar change, after flow crystal thyratron V0 automatic cutout. After the host loop current falls to zero, after time release rectifier and inversion crystal thyratron. Trades in the force flows the stage, mainly examines the rotor position through the encoder, thus triggers the corresponding crystal thyratron, causes the inversion crystal thyratron lead angle is zero, enhances the start torque.
                        
     When the electrical machinery accelerates to the rated speed 10% to 14% (5Hz to 7Hz), 逆变?flows the way from to force to trade the class to cut the counter electromotive force nature 换相, has completed 换相 the way transformation. Namely through the indirect examination synchronous motor stator winding induced electromotive force indirect computation rotor position, may like this the higher control precision.
                        
     Synchronous motor when low speed section movement, inverts the bridge crystal thyratron to continue to lead passes the time quite to be long, easy heat. When air blower low speed the load is lighter, direct current limit value hypothesis in crystal thyratron nominal current 20%. Waits the rotational speed to rise to 10% litre presses when the transformer is at puts through the condition, the electric current limit cuts to 50%, when the rotational speed promotes to 17% after, cuts the electric current limit value in the fixed magnitude of current, while this, in order to enhance the system the efficiency and the mean moment, excitation way by exciting current maintenance constant, changes the magnetic flux maintenance to be constant. When the synchronous motor accelerates to rated speed 95%, the system enters 整步 the fine control stage. The installment sends out from the starting instruction starts automatic 整步 trimming lasted approximately 90s.
                        
     After enters 整步 the fine control stage, the lock-on relay basis electrical network voltage and in the synchronous motor terminal voltage two frequencies bad values (Delta f), produces a rotational speed trimming signal, automatically adjusts the DC voltage height which the rectifier outputs, makes the trimming to the synchronous motor rotational speed, causes two 频率?reduces to the target value in. At the same time, the exciting current also by the lock-on relay control, causes the synchronous motor terminal voltage and the electrical network voltage peak-to-peak value difference achieves the target value.
                        
     Through to the synchronous motor terminal voltage peak-to-peak value, the frequency trimming, causes the synchronous motor stator terminal voltage and difference of value the electrical network voltage achieves time the following target: Delta f<1/4Hz, Delta U<2% UN, Delta S gamma ?0 (Delta S gamma for 相位?, the synchronized incorporation condition namely considers the establishment. The system blockade rectifier and the inversion completely trigger pulse, the output current drops zero. At the same time, the electric motor merges the electrical network, afterwards firing set power source side and the load side switch minute breaks, conclusion starting process. 整步 trimming stage lasted approximately 20s to 40s.
                       
      4  breakdowns phenomena and primitive treating processes
                        
     4.1 incorporations overtimes breakdown
                        
     (1) breakdown phenomenon
                        
     The incorporation overtime is debugs the stage, and goes into production a breakdown which the initial period comparatively often appears. The main phenomenon is, after the rotational speed approaches 1000r/min, cannot incorporate causes the starting overtime defeat; In 整步 the stage exciting current is 85A to 130A between, obviously is bigger than the acceleration period 70A to 75A between.
                       
      (2) fault analysis
                       
      May know according to the synchronous motor rotational speed formula:

According to this in new window browsing picture
      In the formula: N electrical machinery rotational speed;
                             
     U2 rectifier input voltage;
     Alpha Rectifier phase shifting control angle;
     Id direct current return route electric current;
     The r0 inversion 换相 lead angle namely each interphase current initial station is opposite to this nature 换相 angle;
     U inversion trades flows 重叠?
     Phi Air gap magnetic flux.
     Rotational speed n and the air gap magnetic flux phi will have the inverse ratio, if air gap magnetic flux phi oversized, will be able to suppress the rotational speed the rise, will enable the rotational speed not to be able to achieve the rated value, will cause the incorporation overtime starting defeat. After the analysis, the test 整步 incorporation stage exciting current greatly has two main reasons:
   
     如前所, when enters 整步 the incorporation stage, the excitation control mode transfers by the permanent magnetic flux take the electrical network voltage as the goal adjustment electrical machinery terminal voltage. Its target is causes the electric motor terminal voltage U end and the electrical network voltage U net error in 2%. When rotational speed n is bigger than 95% cuts 整步 the stage from the acceleration period, because rate of voltage rise far quickly to rotational speed ascending velocity, when like this causes n approximately is 95%, U end = (100%-2%) U net, also is the air gap magnetic flux phi big, namely the exciting current is big, moreover so long as the U end the exciting current no longer carries on the adjustment in (100%±2%) the U net scope, when finally causes n=100%, electrical machinery terminal voltage nearby on limiting value.
             
      Carries on the test to the lock-on relay to discover its voltage peak-to-peak value match is obviously unreasonable, its peak-to-peak value match is 1.05U the net = U end. Adds the preceding factor the influence, causes the incorporation voltage peak-to-peak value control goal actually is 1.07U the net = U end, causes the exciting current oversized, other situations slightly have the change, rotational speed n cannot achieve the rated value, causes the incorporation defeat.
     (3) countermeasure measure
     
     According to this situation the lock-on relay voltage peak-to-peak value match adjustment is 0.975U the net = U end, 整步 the stage exciting current obviously drops, is 70A to 85A between, eliminated the incorporation defeat phenomenon.
                        
     4.2 encoders breakdowns
                        
     (1) breakdown phenomenon
                        
     On July 1, 2001, because other breakdowns cause three to agglutinate 1#, at the same time the 2# host platoon the engine off, after the main platoon meets the starting requirement, starts the 1# host platoon, inverts the control unit MC2315 appearance in the starting process "ERR2" the breakdown (zero electric current overtime), causes the starting defeat. Then starts the 2# host platoon, similar breakdown starting defeat.
                        
     (2) fault analysis
                        
     The zero electric current overtime usually is because the rotor position examines the mistake or the MC2315 board breakdown causes. Here uses the photoelectricity encoder survey rotor position and the rotational speed, this kind of equipment thermostable ability is bad, because the continual high temperature weather, the environment hyperpyrexia, continues in 65° above. According to 点检 inspected the record, the encoder signal 7, 8 channels already was not the standard square-wave, the performance remarkable deterioration. Basic may conclude the breakdown is because the encoder signal irregularity causes. Because the replacement encoder time is longer, may consider first cools the encoder, the observation use effect, then decided whether replaces the encoder.
                        
     Triggers the angle cancellation when the synchronous motor noramal work, the encoder measured the fast function, closes the encoder power source. Simultaneously improves in the workshop to ventilate the condition, reduces the ambient temperature. Lengthens the encoder life.
                       
      4.3 crystals thyratrons short-circuit the breakdown
                        
     (1) breakdown phenomenon
                        
     In July, 2001 some fortification ended, starts the 1# host platoon, discovered the electric motor is motionless, according to tightly stops the button termination starting. After carries on some inspections, starts the 2# host platoon, the breakdown phenomenon is invariable. The concrete phenomenon is: After the electric motor excitation investment, the electric motor sound responded normal (has electric current to pass). After the main return route invests, the electric motor sound response is normal, but does not rotate. The firing set direct current demonstrated and hypothesis 440A slightly has the deviation.
                        
     (2) fault analysis
                       
      Starts the 1# host platoon electric motor to be motionless. Creates this kind of situation the possible reason to include: Does not have the exciting current or the exciting current insufficient, has not advocated the loop current or the host loop current insufficient, the encoder position examination is not correct, but also has the electric motor itself question to create the starting torque to be insufficient.
                       
      Because in successively and recent surely repairs, the electric motor machinery, the electrical parameter are completely normal, moreover also is two Taiwan Telegraphic Transmission motive similar breakdown, may temporarily not consider electric motor itself in here. Urges the floppy disk electric current demonstration normally, the electric motor diode breakdown has not reported to the police, when exciting current investment electric motor sound normal, may think the excitation return route is normal.
                       
      First replaces the encoder, after but replaces the encoder to start the 1# host platoon breakdown phenomenon to be invariable, explained has nothing to do with with the encoder. The electric motor electric current sound response is normal, explained the electric current truly has flowed the stator coil. We discovered the three phase ac 进线electric current is not balanced. Carries on the inspection to the rectifier, discovered 软起?in the installment rectification bridge the 1# crystal thyratron short-circuits. The replacement crystal thyratron, the starter movement is normal.
                       
      To falls presses the transformer, the crystal thyratron carries on the inspection, discovered 软起?the installment rectification bridge 1# crystal thyratron short-circuits, rectification bridge schematic diagram like chart 2 shows. 

According to this in new window browsing picture
Chart 2    crystal thyratron rectification bridge schematic diagram


                        
     In this equipment, the rectifier uses the speed, electric current Shuanghuan controls, does not have the direct examination direct current return route the electric current, but is exchanges the return route electric current through the examination to calculate the direct current. The rectification bridge crystal thyratron work order is in turn 12, 23, 34, 45, 56, 61, if the 1# crystal thyratron penetrates, in 12 leads passes the period, the direct current return route has the electric current to flow, thus has the electric current in the electrical machinery stator coil to flow. As a result of starting current restriction in 20%, but the electrical machinery speed is zero, namely the counter electromotive force is zero, therefore the rectifier crystal thyratron triggers the angle quite to be big. When triggers the 3# crystal thyratron, because ab by way of 1#, the 3# crystal thyratron short-circuits, the direct current return route does not have the electric current to pass. Falls presses the transformer short-circuit impedance to be very big (8.6%), has limited the short-circuit current; At the same time, because the alternating current increases, the system idea figures out the direct current feedback to increase, the control system through the adjustment, promptly adjusts the crystal thyratron to trigger the angle, triggers when the next crystal thyratron, triggered the angle to be very big, limits the alternating current to continue to increase, therefore the corresponding crystal thyratron, the quick melt has not had the chain-reaction damage. Because actual flows in the electrical machinery electric current not to be big, enables the electric motor to start.
                        
     (3) breakdown lesson
                        
     Because the direct current ammeter undulation not promptly observes, on was objective has increased the breakdown processing difficulty. As well as because subconscious believed, the crystal thyratron short-circuits can have the correlation crystal thyratron and correspond the quick melt the chain-reaction, causes the breakdown magnification, therefore on is subjective has not taken the possibility which the crystal thyratron penetrates, also increased the breakdown process time in the certain degree. But in fact because has used the Gao Lougan special-purpose transformer, occurs when short-circuits the accident, has limited the short-circuit current, simultaneously the electric current assigns only has the rating 20%, has limited alpha the angle, also reduced the short-circuit current harm.
                        
     (4) countermeasure measure
                       
      Each time the main platoon pre-operational, must survey the crystal thyratron resistance number; In the start process carries on the monitoring to the three-phase current.
                       
      5  concluding remark
                        
     The Baoshan Steel Corporation three agglutinates the host exhaust air blower in to go into production the initial period, the starting defeat breakdown are more, above is several quite typical breakdowns. We have not relied on the outside, independently solves the problem which in the system exists. Besides has taken the measure which front states, but also surely is being repaired, carries on the on-line adjustment experiment according to the plan branch to all spare parts, the guarantee complete spare parts supply, as well as familiar equipment performance. In three years, already has not recently broken down starting defeat.
                        
     The frequency conversion starts the large-scale synchronous motor, the starting steady, completely has not also attacked to the electrical network, the reliability is high, domestic and foreign has applied quite widely. This kind of equipment maintenance, breakdown processing also becomes an important research topic, if the method, the measure are appropriate may effectively reduce the maintenance of equipment cost, reduces the fault time.

Author: Baoshan Steel Corporation stock Baoshan Steel Corporation subsidiary company ironworks Wang Zhikun Baoshan Steel Corporation stock Baoshan Steel Corporation subsidiary company equipment department Huang Zhigang
Information origin: China industrial equipment net
Chief-editor: Article author:

In data increase......

Hot spot article
Howselects and purchases the frequency changer
Programmable controller installment and maintenance
PLC and the frequency changer connect when should pay attention question
Reaches the mechanical and electrical product on fuel gas type food tunnel type furnace conformity application
Programmable foreword controller five kind of standards programming language
The new -odd iron and steel company raw material stands, rolls over 钢站 the microcomputer interconnection and the monitor system
The Daya Bay nuclear power station KIT data accesses the net the transformation monitor system
The low pressure turbine oil pure electricity moves with the high-pressured anti- fuel oil pure electricity accent compares
One kind of new main line system CAN
Our country industry control automation technology present situation and tendency
In data increase......
Website map
Copyright 2006-2008