Introduction

   In the bag filter project has 8 50kW to enter the branch to pump, 4 30kW reflux pump uses the Fuji frequency changer velocity modulation, the bag filter entire work process controls the room by the host the FOXBORO collection systems control. Feed pump frequency conversion velocity modulation movement to split-ring condition, through DCS collection system hypothesis frequency value control current capacity; Reflux pump frequency conversion velocity modulation movement to closed loop condition, control backflow tank liquor position. In the test run process, the feed pump, the reflux pump frequency changer trips one after another, on the frequency changer display monitor demonstrated "OU2 decelerates when 过电?. The feed pump trips the reason is because the bag filter craft reason creates the feed pump load suddenly to reduce; The reflux pump when 2-3 bag filter to filters the cloth counter- flushing, circulation 卸料, time short, the current capacity is big, in the branch thick liquid mixes has the air, causes the reflux pump idle operation, the load suddenly reduces, causes the electrical machinery to be in 再生制动 the operating mode, causes the frequency changer middle direct current return route 过电? the frequency changer protection trips. Although has taken some measures in the test run stage, but the breakdown hidden danger eliminates by no means, needs to consider uses the cost to be lower, the structure simple resistance braking unit.

In deals with this issue in the process, is altogether used many frequency changers the identical direct current generatrix to solve this question enlightenment, we to the feed pump, the reflux pump from the craft, on the frequency conversion velocity modulation system have carried on some modification, better solution frequency conversion velocity modulation system middle direct current 过电?question.

1 pair of reflux pump system processing

(1) the reflux pump was because in the material thick liquid mixes in the air 打空?to initiate the breakdown, in the electrical system aspect mainly was because the reflux pump was at the closed loop running status to create, changed the reflux pump frequency changer by the closed loop running status the split-ring movement way then to be possible to solve this breakdown. Namely controls the room in the host on the FOXBORO collection system to return to the launder to establish Gao Kewei, to compare Gao Kewei, the lower material position, the low material position 4 materials positions parameter, causes the reflux pump when the lower material position the low speed movement, compares when Gao Liaowei the high speed movement, the frequency changer adds, decelerates time item to lengthen is 60s, causes the reflux pump frequency conversion velocity modulation system not to expect the thick liquid current capacity the instantaneous change to change.

(2) in the craft aspect, to returns to the launder place in each bag filter backflow exportation to add the cushion trough, the change backflow current capacity sudden change condition, reduces the current capacity change to the frequency changer the influence.
Processes after above, the reflux pump has been able stably to move, thorough settlement middle direct current return route 过电?question. 2 pair of feed pumps systems processing original system 8 bag filters divide into 2 groups, 4 feed pumps and 2 reflux pumps are a group, the normal time each group has 2-3 to enter the branch to pump in moves with 1 reflux pump, each group has 1 reflux pump to do spare, each group of 6 equipment coexist in section of exchanges generatrixes. Because each group has 1 reflux pump long-term movement, after therefore passes through the above processing to move very stably. We use the reflux pump frequency conversion system for to enter the branch to pump the frequency conversion system 再生制动 time the energy which produce in the middle direct current return route to provide 泄放 the circuit.

(]) 4 feed pumps and 2 reflux pumps frequency changers power source side alternating voltage all is 380V, the middle DC voltage is about 310V, basic is mutually same, can have the load and the frequency control influence the undulation. If each frequency changer middle direct current return route directly connects, after the middle direct current return route system allows the quantitative change to be big can bring many advantage, for example: The middle DC voltage is relatively constant, after the electric capacity parallel stored energy capacity enlarges; Enhances the system the power factor and the system uses electricity the efficiency, reduces the electrical network the harmonic current; Between various frequency changers the capacity may supplementary, 再生制动 the condition produces the unnecessary energy may by other frequency changer absorptions, the transformation, when the normal operation cannot create the frequency changer middle direct current return route 过电?to trip, optimized system dynamic characteristic and so on. But because the frequency changer power source side has used not the controllable rectification bridge, has flowed the rectification bridge electric current not not controllably, even can surpass the electric current which its can withstand to damage: Directly altogether uses the middle direct current return route, short-circuits the breakdown when the phylogeny, because the rectification bridge partial protections less also the sensitivity is bad, each frequency changer cannot promptly excise, can cause the breakdown further to expand, causes a bigger losses. Therefore directly connects time the middle direct current return route, the frequency conversion velocity modulation system can change is unreliable. Electric circuit uses the diode, the contact device main goal in chart in 1 is for prevent the frequency conversion system because altogether to use the direct current generatrix to initiate the breakdown, achieved both has been able to eliminate the breakdown, and did not reduce the frequency changer reliable goal.

(2) feed pump frequency changer return route diode 管主 if causes between each feed pump frequency changer to be mutually independent in the movement, mutually does not affect, 再生制动 the condition produces energy by noramal work reflux pump consumption, realization energy full use.

The contact device uses for to realize the frequency changer with altogether to use the direct current generatrix, mutually connects, the power failure and the overhaul when the frequency changer movement mutually isolates; When breaks down the prompt excision with altogether uses the direct current generatrix the relation.

(3) 2 reflux pumps in

Often moves when for as soon as uses as soon as to prepare, in order to prevent also moves in the peculiar circumstance next 2 reflux pumps, with altogether used the direct current generatrix in 2 reflux pumps frequency changers middle direct current return route to increase the diode, enabled 2 reflux pumps mutually to isolate, reduces the breakdown.

(4) in normal condition feed pump frequency conversion velocity modulation system to backflow frequency changer middle direct current return route feed, because enters the branch to pump the frequency changer to be bigger than the reflux pump, also has the certain remainder, when normal operation cannot create the harm to the feed pump frequency changer, only has in the reflux pump rectification bridge shuts or altogether uses in the situation which the direct current generatrix occurs short-circuits, only then can have the fault current inflow middle direct current generatrix, in this kind of situation, this return route mainly depends upon frequency changer itself each kind of protection namely using frequency changer breakdown signal 3 0C, 30B causes the contact device movement which increases in each frequency changer return route, promptly with altogether uses the frequency changer the generatrix to excise, Avoids breaking down bigger.

(5) in the return route increases the diode selects ordinary rectification diode ZP20, the passing condition mean current is 20A, can withstand the surge current may reach 150-200A, each frequency changer middle DC voltage basically about 310V, 再生制动 the condition produces too much the electric current although peak-to-peak value big somewhat, but time short, the diode withstands the electric current with directly meets in the middle direct current generatrix beginnings and ends resistance braking unit is different, selects the ZP20 diode to add the radiator to be able to satisfy the electric circuit request.

(6) because increases the contact device must shut off under the malfunction altogether uses the big electric current which between the direct current generatrix and the frequency changer possibly has, 1 ~ 6KM selects the CJ-50 exchange contact device.

(7) in order to prevent the reflux pump frequency changer middle direct current return route in pours into when the big electric current which possibly has 过电?trips, adopts: (1) Controls the room while the host on the FOXBORO collection system to take the measure to prevent each group of movements 2-3 bag filter instead; Center washes unloads the branch, causes each bag filter 卸料 instead; Center washes the time is separated by 3-5min. (2) In altogether uses in the direct current generatrix installs 1 group of resistance braking unit, maximum limit reduces the reflux pump frequency changer middle direct current return route 过电?probability, safeguards the bag filter frequency conversion system movement the security.

(8) when construction had considered the middle direct current return route possibly short-circuits the situation, selects the high quality insulation cab-tire cable to make the ties, strengthened the insulation in the part, reduced the probability which the middle direct current return route earth short-circuits.

(9) frequency changer movement environment better, 10 frequency changers have the special-purpose frequency changer room, in the room install 2 cabinets types air conditioning, clean is neat, is advantageous to the frequency changer radiation and the reduced frequency changer breakdown probability.

3 concluding remark

This electric circuit after the actual movement, the effect is better. This improvement program has realized the bag filter frequency conversion system stable movement with less ordinary parts, has omitted the multi- wraps resistance braking unit, enable the electrical machinery 再生制动 energy to obtain the full use, was processes the frequency changer 再生制动 energy and the breakdown effective way. 

Information origin: China industrial equipment net
Chief-editor: Article author:

In data increase......

Hot spot article
The collection control system (DCS) introduces
Whichaspects does the choice digital oscilloscope have to pay attention to
Flexible manufacture system essential technology and development tendency
FOPLC controls more than 3,000 equipment nimble revolutions
The North China branch mechanic controls the product in jail supervisory control system application plan
The North China labor controls NORCO labor controlling machine in the bank call center service application
The strength controls the strategy controller to blow off in the interconnection in the torch the application
Howchooses the low cost automated system
Frequency changer breakdown code comparative table
NOVO-5845 in sells the card machine multimedia center the application
In data increase......
Website map
Copyright 2006-2008